TIMER_ – Multipurpose timer
Block SymbolLicensing group: STANDARD
Function Description
The TIMER_ block either generates an output pulse of the given width pt (in seconds) or filters
narrow pulses in the U input signal whose width is less than pt seconds. The operation mode is
determined by the mode parameter.
The graph illustrates the behaviour of the block in individual modes for :
The timer can be paused by the HLD input. The R1 input resets the timer. The reset signal overpowers the U input.
Inputs
U | Trigger of the timer | Bool |
HLD | Timer hold | Bool |
R1 | Block reset () | Bool |
Outputs
Q | Timer output | Bool |
et | Elapsed time [s] | Double (F64) |
rt | Remaining time [s] | Double (F64) |
Parameters
mode | Timer mode 1 | Long (I32) |
|
|
|
pt | Timer interval [s] 1.0 | Double (F64) |
[Previous] [Back to top] [Up]