TIMER – Multipurpose timer
Block SymbolLicensing group: STANDARD
Function Description
The TIMER block either generates an output pulse of the given width pt (in seconds) or filters
narrow pulses in the U input signal whose width is less than pt seconds. The operation mode is
determined by the mode parameter.
The graph illustrates the behaviour of the block in individual modes for pt=3:
The timer can be paused by the HLD input. The R1 input resets the timer. The reset signal overpowers the U input.
Inputs
U | Trigger of the timer | Bool |
HLD | Timer hold | Bool |
R1 | Block reset (R1=on) | Bool |
Outputs
Q | Timer output | Bool |
et | Elapsed time [s] | Double (F64) |
rt | Remaining time [s] | Double (F64) |
Parameters
mode | Timer mode ⊙1 | Long (I32) |
|
|
|
pt | Timer interval [s] ⊙1.0 | Double (F64) |
[Previous] [Back to top] [Up]